Worcester 28i Junior Especificaciones Pagina 2

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 22
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 1
43
20. Conversion Instructions
NOMINAL BOILER RATINGS (10 Minutes After Lighting)
BOILER ADJUSTED FOR G20 (Natural Gas)
OUTPUT INPUT (Net) GAS RATE
kW kW m bar. m
3
/h
8.0 9.5 1.2 1.00
27.5 30.0 14.7 3.17
BOILER ADJUSTED FOR G31 (Propane)
8.0 9.5 3.4 0.39
27.5 30.0 35.3 1.23
Table 1. 28i
BURNER
PRESSURE
NOMINAL BOILER RATINGS (10 Minutes After Lighting)
BOILER ADJUSTED FOR G20 (Natural Gas)
OUTPUT INPUT (Net) GAS RATE
kW kW m bar. m
3
/h
3.5 9.5 1.4 1.00
23.5 25.9 13.6 2.74
BOILER ADJUSTED FOR G31 (Propane)
7.5 9.5 4.6 0.39
23.5 25.9 35.0 1.06
Table 1. 24i
BURNER
PRESSURE
Natural Gas: Net Input = Gross Input x 0.901 LPG (Propane): Net Input = Gross Input x 0.922
ONLY COMPONENTS SUPPLIED BY WORCESTER HEAT
SYSTEMS SHOULD BE USED
ONLY COMPETENT PERSONNEL SHOULD ATTEMPT THE
CONVERSION
CONVERSION FROM NATURAL GAS TO LPG SHOULD NOT BE
CARRIED OUT ON APPLIANCES INSTALLED IN A ROOM OR
INTERNAL SPACE BELOW GROUND LEVEL
1. Ensure the gas service cock is turned OFF and the electrical
supply is ISOLATED.
2. Refer to the Servicing Instrucions to remove the cabinet front
panel and inner casing.
3. Follow the dismantling instructions to remove the burner.
Refer to Installation and Service Instructions Section: Inspection
and Servicing.
4. Remove the injector and replace with the relevent injector
from the kit. Refer to Installation and Service Instructions
Section: Inspection and Servicing.
5. Remove the nut end cap and bracket at the opposite end of
the burner and insert the gauze from the kit for NG to LPG or
remove it for LPG to NG.
6. Refit the end cap ensuring that the support bracket is in the
correct orientation.
7. Remove the gas valve and replace with the gas valve
supplied in the kit. Refer to Installation and Service Instructions
Section: Replacement of Parts.
8. Re-assemble the burner and inner-casing.
9. Turn on the gas and electricity supplies and follow the
commissioning procedure to confirm gas soundness and correct
boiler operation.
10. Check and adjust the setting pressures to the values in the
table overleaf and adjust if necessary. Refer to Installation and
Service Instructions Section: Replacement of Parts. “To Set the
Burner Pressure”.
11. Refit the plastic sealing cap to the gas valve modulating
valve adjuster and seal with a dab of paint or similar.
12. Turn off the boiler and when cool peel off the arrow from the
data plate on the combustion chamber front panel and re-stick
against the gas type for which the boiler has been converted
and adjusted.
13. Replace the boiler front panel.
The conversion is now complete.
Max
2mm
Allen key
Min
3mm
Allen key
Gas valve
sealing
cap
Burner
pressure
test point
Electrical
connections
modulator
(Blue:Blue)
Clockwise to
increase
Anti-clockwise
to decrease
Slight
movement
only
is
required
Inlet
pressure
test point
Main gas
valve
connections
QTY DESCRIPTION PART No
1 Conversion Instructions
1 LPG Gas Valve Dungs BM771 sl 040 (for LPG to NG) 8 716 105 654
1 NG Gas Valve Dungs BM771 sl 040 (for NG to LPG) 8 716 105 650
1 Burner gauze 8 716 142 601
1 Fibre washer 8 710 103 043
2 O rings 8 716 140 827
1 Injector 2.7mm 24i LPG 8 716 156 373
1 Injector 2.78mm 28i LPG 8 716 140 209
1 Injector 4.3mm 24i NG 8 716 105 033
1 Injector 4.5mm 28i NG 8 716 140 208
1 Copper washer 8 716 101 994
The appliance is suitable for installation in GB and IE only and
should be installed in accordance with the rules in force.
1.1 Gas Safety (Installation & Use) Regulations 1998:
It is the law in GB that a competent person in accordance with
the above regulations installs all gas appliances.
Failure to install appliances correctly could lead to prosecution.
It is in your interest, and that of safety, to ensure compliance
with the law.
1.2 The manufacturers notes must not be taken, in any way, as
overriding statutory obligations.
1.3 The compliance with a British Standard or European Norm
does not, in itself, confer immunity from legal obligations.
1.4.1 The installation of the appliance must be in accordance
with the relevant requirements of the Gas Safety Regulations,
current IEE Regulations, Building Regulations, Building Standards
(Scotland) and local water by-laws.
1.4.2 In Eire, the installation must be carried out by a competent
person and installed in accordance with IS813, Domestic Gas
Installations (Edition 2), the current Building Regulations and the
electrical installation must follow the ETCI rules.
1.5 The installation should follow the recommendations of the
following British Standards unless otherwise indicated.
BS5440:1 - Flues and ventilation for gas appliances: Flues
BS5440:2 - Flues and ventilation for gas appliances: Air supply.
BS5449 - Central heating for domestic premises.
BS5482 - Domestic propane gas burning installations.
BS5546:1 - Installation of gas hot water supplies.
BS6700 - Domestic water supply in buildings.
BS6798 - Installation of gas fired hot water boilers.
BS6891 - Low pressure gas pipework installations upto 28mm
(R1).
BS7593 - Water treatment.
BS7671 - Requirements for electrical installations (16th Edition).
British Standards and Regulations are not in force in Ireland,
however useful information relating to the hydraulic aspects of
heating systems may be found in IS 813: Annex M and in
BS5546, BS5449, BS7074 and BS7593.
1.6 The appliance and components must conform, where
applicable, to all relevant Directives.
1.7 The appliance does not contain any substances which are
harmful to health.
1.8 In certain circumstances, the installer can be held
responsible, not only for mistakes on his part but also for
damage resulting from the use of faulty materials. We advise
that, to avoid any risk, only quality approved branded fittings
and the specified replacement parts are used.
1.9 LPG Installation:
The appliance shall not be installed in a room or internal space
below ground level when it is intended for use with LPG. This
does not preclude the installation into rooms, which are
basements with respect to one side of the building but open to
the ground on the opposite side.
1.9.1 CARAVAN AND HOLIDAY HOMES
The installation must meet the following standards.
BS5482:2 LPG and EN721 ventilation.
1.9.2 PARK HOMES AND RESIDENTIAL
The installation must meet the following standards.
BS5482:1 LPG and BS3632 ventilation.
1.10 These instructions cover, as far as possible, the foreseeable
situations, which may arise.
Contact Worcester, Bosch Group Technical Department,
Telephone: 08705 266241, for advice on specific installations.
In Eire call 01 494 0099.
2.1 The Benchmark initiative is the new code of
practice to encourage the correct installation, commissioning and
servicing of domestic central heating boilers and system equipment.
The 'Log-book' is a vital document that must be completed
by the installer at the time of installation. It confirms that the
boiler has been installed and commissioned according to the
manufacturers instructions.
A Declaration of Conformity (refer to IS813 Annex D 1) must
be completed by the installer and a copy supplied to the
appliance operator for boilers installed in Eire.
Without the completion of the Log-book and/or Declaration,
manufacturers may refuse to respond to a call-out from a
householder, who will be advised that he or she must call back the
installer, who has not fulfilled his obligations to record the
information required by the initiative.
Service:
To ensure the continued efficient operation of the appliance it must
be checked at regular intervals. The frequency of servicing will
depend upon the particular installation conditions and usage, but
once per year should generally be adequate. The extent of the
service required by the appliance is determined by the operating
condition of the appliance when tested by fully qualified engineers.
Any service work must be carried out by competent registered
(by CORGI in GB) engineers.
2.2 General Information
The appliance is set to give the maximum output of 27.5 kW [28i] or
23.5kW [24i] to the domestic hot water and to the heating system.
The hot water flow rate is limited to a nominal 10 l/min [28i] or 8
l/min [24i] at a maximum temperature rise of 40°C.
The sanitary water section of the appliance is suitable for a mains
water pressure of up to 10bar.
An internal filling loop assembly approved by the WRAS is an
optional extra.
The 28i is only manufactured for use with Natural Gas.
Kits are available for the 24i and 28i appliances to convert from
Natural Gas to LPG operation and vice versa.
1. Installation Regulations
2
1. Installation Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2 11. Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 10
2. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2 12. Installing the Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . Page 13
3. Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 5 13. Commissioning the Appliance . . . . . . . . . . . . . . . . . . . . Page 20
4. Siting the Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 8 14. Handover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 22
5. Flue Terminal Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 8 15. Inspection and Service. . . . . . . . . . . . . . . . . . . . . . . . . . . Page 22
6. Air Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 9 16. Replacement of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 25
7. Sealed System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 9 17. Short Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 31
8. Open Vent System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 9 18. Operational Flow Diagrams. . . . . . . . . . . . . . . . . . . . . . . Page 33
9. Domestic Hot Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 10 19. Fault Finding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 35
10. Gas Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 10 20. Conversion Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . Page 43
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents
2. Introduction
Vista de pagina 1
1 2 3 4 5 6 7 ... 21 22

Comentarios a estos manuales

Sin comentarios